Proper operation and maintenance can extend the life of the radiator and ensure its heat dissipation effect. Key points include:

1.Regular Cleaning: Clean the radiator surface of dust and oil every 3-6 months (outdoor transformers can be washed with a high-pressure water gun, and indoor transformers can be blown out with compressed air) to prevent increased thermal resistance. If the environment is dusty, install a dust filter.

2.Sealing Check: Check the flanges and valves connecting the radiator and the oil tank annually to prevent insulating oil leakage (leakage will reduce oil volume, insufficient heat dissipation area, and increased oil temperature). Replace the sealing gaskets immediately if leakage is found.

3.Fan/Oil Pump Maintenance: For air-cooled/forced oil-cooled transformers, check the fan speed and noise every 1-2 months (insufficient speed will reduce airflow and decrease heat dissipation efficiency). Check the oil pump's operating status every six months (for jamming or abnormal noise) to ensure the forced circulation system is working properly.

4.Troubleshooting: If the top layer oil temperature of the transformer rises abnormally, first check the radiator:

① Check if the surface is heavily dusty;

② Test if the fan/oil pump starts normally;

③ Check if the oil level is normal (too low an oil level will cause insufficient oil flow in the radiator);

④ Use an infrared thermometer to check the temperature of each part of the radiator. If the local temperature is too high, it may be due to internal blockage (such as oil sludge accumulation), which requires disassembly and cleaning.info-639-480